Friday, January 22, 2010

Steam velocity

A recommended maximum velocity
for steam to prevent erosion from condensate? Prevent noise?

"Engineering Data Reference Tables"
Saturated Steam 1-15 psig Heating Mains 4000-6000FPM
Saturated Steam 50-up psig Misc 6000-8000FPM
Saturated Steam 200-up psig Turb&Boiler leads 10K-15K